NOTT AC-HTPF60 Fresh Air Heat Pump
€4 650,00
NOTT – DC Inverted Fresh Air Heat Pump
Description
FLIXX NOTT AC-HTPF60 includes:
– Intelligent air quality sensor
– Electric pre-heater
– CO2 sensor
– Humidity sensor
– Wi-Fi
– VOC sensor
– Electronically controlled fan
– Counter-flow enthalpy heat exchanger
Advantages:
Up to 90 % Heat + 80 % Humidity RecoveryCross-counterflow enthalpy heat exchanger recovers heat and moisture from the exhaust air without mixing streams. Washable, anti-mold membrane rated for up to 15 years — no frosting down to −30 °C, condensate-free in normal conditions. |
DC Inverter Compressor (GMCC)Adjustable-speed DC inverter compressor matches output to load — higher efficiency, quieter operation, smoother start-stop and faster temperature control than fixed-frequency compressors. Operating range −15 °C to 50 °C. R32 refrigerant. |
EC Fans — 10 SpeedsForward EC motors with 0–10 V control, 10 speeds, low vibration and low noise (from 37 dB(A)). Meets ErP 2018 ecodesign requirements for energy-efficient ventilation. |
100 % Auto BypassMotorised bypass opens automatically in summer when outdoor conditions allow free cooling without heat exchange — controlled by the outdoor temperature sensor, no manual switching needed. |
Multi-Stage FiltrationStandard G4 primary + F8 fine filters remove dust, pollen and PM2.5 (over 95 % filtration efficiency) before air reaches the heat exchanger. Optional air-disinfection filter available for higher filtration. |
A Energy Class · ErP 2018Verified per EU Ecodesign Regulation 1254/2014: all three NOTT models — FAHP-35, FAHP-60, FAHP-90 — rate Energy Class A, with internal & external air leakage under 5 %. |
TECHNICAL DATA
| Rated airflow, m³/h | 620 |
| External static pressure, Pa | 100 |
| Recovery type | Enthalpy (HPERV) |
| Temperature efficiency (heating), % | 78 |
| Temperature efficiency (cooling), % | 72 |
| Enthalpy efficiency (heating), % | 77 |
| Enthalpy efficiency (cooling), % | 65 |
| Input power (ventilation mode), W | 451 |
| Input current (ventilation mode), A | 3.77 |
| Nominal cooling capacity, kW | 6.4 |
| Input power (cooling), kW | 1.24 |
| EER | 5.14 |
| Nominal heating capacity, kW | 6.3 |
| Input power (heating), kW | 1.03 |
| COP | 6.09 |
| Compressor / fans | DC inverter compressor · EC fans |
| Power supply | 220 V~ / 50–60 Hz, 1 Ph |
| Sound power level, dB(A) | 40 / 44.6 |
| Refrigerant | R32 |
| Refrigerant charge, g | 500 |
| Unit dimension W×L×H, mm | 740×1050×990 |
| Air inlet / outlet diameter, mm | 245 |
| Net weight, kg | 165 |
Information from the manufacturer