FRIGG FAH-650 horizontal energy recovery ventilation unit
€1 855,00
The FLIXX FRIGG ceiling fan with energy recovery is made from the finest materials and boasts first-class workmanship.
Description
FRIGG FAH-650 package includes:
– Electric pre-heater
– CO2 sensor
– Humidity sensor
– Wi-Fi
– H10 filter
– DC fan
– Touch controller
– App control
– Enthalpy heat exchanger
– Modbus protocol
– Automatic bypass function
– Automatic control based on humidity, CO2 and VOC
Advantages:
Up to 90% energy recoveryThe 3D cross-counterflow enthalpy exchanger transfers both heat and moisture from three directions – maximizing surface area and energy recovery efficiency during both the heating and cooling periods. |
Enthalpy exchanger (ERV) – standardThe polymer enthalpy membrane conducts both heat and humidity in all units – standard equipment, no additional equipment required. Up to 87% enthalpy efficiency, no air drying in winter, condensate does not freeze below −30 °C, no condensate drainage required. |
DC fans with constant airflowAll eight FAH models feature 10 variable speed DC fans with constant airflow compensation – automatically maintaining rated airflow regardless of duct static pressure or filter load. Up to 40% energy savings compared to AC motors. |
A-energy classVerified based on official EU energy labels (Regulation 1254/2014): All eight FRIGG FAH models – FAH-250 to FAH-2000 – belong to energy class A according to the current ecodesign assessment. |
100% automatic BYPASSIn summer, the motorized bypass valve opens automatically when the outdoor temperature is within the adjustable comfort range – supplying the unit with fresh air without heat exchange, ensuring free-cooling ventilation. |
RS485/Modbus and BMS integrationIn addition to standard WiFi / Smart Life app control, FRIGG FAH devices also have RS485 / Modbus connectivity for building management system integration – suitable for lighter commercial building installations. |
TECHNICAL DATA:
| FAH-650 Advance | |
| AIRFLOW & PRESSURE | |
| Rated airflow, m³/h | 650 |
| Max. external static pressure, Pa | 120 |
| ENERGY RECOVERY (ERV) | |
| Recovery type | Enthalpy (ERV) |
| Temperature efficiency (heating), % | up to 86 |
| Enthalpy efficiency (heating), % | up to 82 |
| Enthalpy efficiency (cooling), % | up to 81 |
| ELECTRICAL & ACOUSTICS | |
| Fan motor | DC Fan · 10 adjustable speeds · Constant flow compensation |
| Power supply | 220–240 V~ / 50 Hz | 120 V / 60 Hz |
| Max. power input, W | 252 |
| Sound power level, dB(A) | 41 |
| Energy efficiency class | A |
| PHYSICAL | |
| Unit dimensions W × L × H, mm | 908×954×404 |
| Duct diameter (nominal), Φ mm | Φ 200 |
| Operating temperature range, °C | −20 to +45 |
| Casing / insulation material | Galvanized steel / EPP |
| Net weight, kg | 38 |